Calculator

UPS Runtime Calculator

Estimate how long a UPS battery carries a load that fits inside its volt-amp rating.

Your inputs

Ah
V
%
W
VA

Watts the UPS can supply are volt-amps times this factor.

Runtime

2 h 24 min

The UPS can supply 800 W at this power factor. Runtime uses amp-hours, voltage, and efficiency.

Runtime
2 h 24 min
Watt limit
800 W

Formula

Usable watt-hours are amp-hours times voltage times efficiency:

hours = amp-hours × volts × efficiency / load watts

The load must also be no more than volt-amps times the power factor. A milliamp-hour gadget battery stays on the battery runtime page.

Assumptions

  • The battery is fully charged.
  • The load is steady.
  • The power factor is the one the UPS maker states for its watt rating.

Worked example

A 100 Ah, 12 volt battery at 80% efficiency, carrying 400 watts on a 1,000 VA unit at 0.8 power factor, runs 2 h 24 min.

Input definitions

Volt-amps
The UPS rating. Its watt limit is that rating times the power factor.
Power factor
The share of the volt-amp rating that is available as watts.

Limitations

This is a planning estimate. The rate, sun hours, and losses are numbers you type. It is not a utility bill, a solar design, or a room-by-room load calculation.

Questions

Why can a 1,000 VA unit reject a 900 watt load?

At a power factor of 0.8 the watt limit is 800. The page will not invent runtime for a load the rating cannot cover.

Is this a phone power bank?

No. Power banks use milliamp-hours on the battery runtime page. This page is a UPS battery in amp-hours, with a volt-amp limit.

Related

Related calculators

Battery

See every calculator in Battery.

Browse Battery